ANFIS-Based Static Var Compensator Control for Voltage Recovery and Rotor-Angle Stability in a 330 kV Transmission Corridor
Itoro E. Udosen *
Electrical and Electronics Engineering Department, University of Uyo, Uyo, Nigeria.
Nseobong I. Okpura
Electrical and Electronics Engineering Department, University of Uyo, Uyo, Nigeria.
Kufre M. Udofia
Electrical and Electronics Engineering Department, University of Uyo, Uyo, Nigeria.
Akaninyene B. Obot
Electrical and Electronics Engineering Department, University of Uyo, Uyo, Nigeria.
*Author to whom correspondence should be addressed.
Abstract
The interaction between voltage depression and rotor-angle acceleration presents a challenge for heavily loaded transmission systems. This study evaluated an adaptive neuro-fuzzy inference system (ANFIS) controller for a static var compensator (SVC) using a MATLAB/Simulink representation of a 330 kV, 250 km transmission corridor. The ANFIS used voltage deviation and its rate of change to produce a susceptance command and was compared with an uncompensated network, a particle-swarm-optimised proportional–integral (PI) SVC and an artificial neural network (ANN) SVC. For the simulated three-phase fault, the ANFIS case exhibited a voltage-dip depth of 0.22 p.u., a voltage recovery-time indicator of 0.8 s, a first-swing rotor-angle excursion of 46°, and a damping ratio of 0.31. Reported critical clearing times were 0.145, 0.195, 0.235 and 0.265 s for the uncompensated, PI, ANN and ANFIS configurations, respectively. At a 0.200 s clearing time, this corresponds to positive clearing margins for ANN and ANFIS control and negative margins for the uncompensated and PI configurations. The results demonstrate the potential of neuro-fuzzy SVC control to improve the voltage and angular-stability indicators examined in the modelled transmission corridor.
Keywords: Adaptive neuro-fuzzy inference system, static var compensator, critical clearing time, voltage recovery, rotor-angle stability, FACTS